Equipment No. . |
|
Manufacturer . |
|
Description . |
|
Manufactured . |
|
Drawings . |
|
Photos . |
|
|
 |
 |
|
Specifications
|
|
|
Turbine- Generator 4 MW Condensing with Extraction
Single- casing- turbine, condenser modified for heating.
Turbine Siemens EK 6,5 /I
Output 3 760 / 4 000 kW
Life- steam design / max 37 / 44 bar, 440 / 460 oC
Extraction 3 +/- 1 bar, 300șC, 0 - 15 t/h
Exhaust pressure design 0.062 bar
Exhaust for heating condenser 0.9 bar, 97șC, 19 t/h
Gear Siemens 4 600 kW
Gear speed 6 500 / 1 500 rpm
Generator Siemens, PFL 380 / 35-4
Aparent power 5 MVA
Voltage 6,3 kV, 50 Hz
Condenser for heating 262 m3/h, 50 - 90 oC
Heating surface 190 m2
Steam flow 19 t/h, 0,9 bar, 97 oC
|
|